top of page
Search

Do You Really Need Crash-Rated Fencing? Here's the Truth for UK Data Centre Security in 2026

Nov 14
5 min read

When it comes to data centre security, a crash rating is not a box to tick just because your site is important. The right protection depends on the threats your perimeter actually faces, and whether a vehicle could reach a critical asset.

I have seen firsthand how easily discussions about perimeter security can become focused on product labels rather than site-specific risk. In 2026, with data centres designated as Critical National Infrastructure (CNI) and standards changing, you need to know what a crash rating proves, what it doesn’t, and when it belongs in your specification.

Does CNI status mean every data centre needs crash-rated fencing?

No. The UK government designated data centres as CNI on 12 September 2024, under the Communications sub-sector, led by the Department for Science, Innovation and Technology. The designation enables prioritised government support during incidents and coordination with security agencies, including the National Cyber Security Centre.

It does not, by itself, require every data centre to install crash-rated fencing.

The Cyber Security and Resilience Bill is introducing mandatory regulatory oversight, including proportionate security measures, incident reporting to Ofcom and operational resilience against physical and cyber threats. That makes evidence-based risk management more important. It does not make one type of perimeter product appropriate for every site.

The practical question is: could a vehicle realistically be driven into a protected area, and what would it reach if it got there?

What does a vehicle crash rating actually certify?

A vehicle security barrier (VSB) rating records the result of a defined impact test. It relates to a particular test scenario, including:

  • The vehicle type and mass

  • The impact speed and angle

  • The distance the vehicle penetrates beyond the barrier

A rating is evidence of performance in that tested configuration. It is not a universal guarantee that a barrier will stop every vehicle or perform identically in every location. Ground conditions, foundations, installation details, barrier layout and the approach route all matter.

It is also useful to be precise about terminology. A crash-rated vehicle barrier is not necessarily a fence. Vehicle protection may involve a barrier, bollards, a gate, or another engineered element. Meanwhile, high-security perimeter fencing is generally intended to deter, delay or resist unauthorised pedestrian entry. These measures address different threats.

That distinction matters when planning data center security solutions: a rating for vehicle impact does not automatically prove resistance to manual attack, and a forced-entry rating does not prove a product can stop a moving vehicle.

What changed in 2026: ISO 22343-1, NPSA and LPS 1175

For new vehicle security barrier testing, ISO 22343-1:2023 has superseded PAS 68 and IWA 14-1. Products tested to the older standards remain valid and acceptable; the change does not automatically invalidate existing installations or evidence.

The standards also present test results differently:

  • Ratings describe the test vehicle, speed, impact angle and penetration distance.

  • PAS 68 measures penetration from behind the barrier and incorporates debris dispersion into its rating.

  • IWA 14-1 and ISO 22343-1 measure penetration from the front of the barrier and report debris separately.

  • The vehicle categories and masses differ between the standards, so a rating under one standard is not directly comparable with a rating under another.

So don’t compare labels alone or assume that two ratings mean identical performance. Ask for the test evidence and understand the scenario it represents. For current guidance, see NPSA’s HVM rating system explained and its guidance on security fences and gates.

There is a separate change for fencing and gates. From 1 January 2026, NPSA removed all fencing and gates from its Catalogue of Security Equipment (CSE) and stopped testing these products against the Manual Forced Entry Standard (MFES). That is a change to NPSA’s catalogue and testing arrangements, not a signal that fencing is no longer useful, or that all fences should be crash-rated.

Specifiers now need to consider independent third-party certification, such as LPS 1175, when verifying forced-entry performance. LPS 1175 relates to resistance against manual attack; it is not a vehicle-impact standard. BS 1722 remains the minimum industry baseline, but relies on self-certification rather than independent testing. For a site with both vehicle and pedestrian attack concerns, you may need to specify and evidence those performance requirements separately.

Illustrative industrial perimeter with green mesh fencing beside a data centre building

When is crash-rated protection genuinely required?

NPSA guidance recommends quantifying the vehicle threat with a Vehicle Dynamics Assessment (VDA), conducted by a suitably qualified specialist. In plain terms, a VDA examines the vehicle, route, speed and impact angle that could apply at a particular location.

Crash-rated protection may be appropriate where the assessment identifies a credible vehicle-impact threat and a vehicle could reach critical equipment or another protected asset. The assessment helps determine the performance needed and where barriers should go.

By contrast, if the principal concerns are trespass, theft or unauthorised pedestrian access, and a vehicle-impact route is not a credible risk, then a crash-rated barrier may not be proportionate. A properly specified high-security perimeter fence, secure gates, access controls and suitable monitoring may be more relevant to the identified threat.

Here’s why the whole boundary matters: a barrier at one point will not protect an asset if an adjacent gate, corner, fence transition or service opening creates an easier route in. Remember, the answer may be a layered system, not a choice between “ordinary fencing” and “crash-rated fencing”.

How fencing, gates and bollards work together

A data centre perimeter has operational demands as well as security requirements. Staff, contractors and deliveries need controlled access, while emergency and maintenance arrangements must still work.

Depending on your site assessment and specification, a coordinated perimeter might include:

  • High-security fencing to define the boundary and resist or delay pedestrian intrusion.

  • Gates that match the required security level while allowing planned vehicle access.

  • Rising bollards or other VSBs at locations where a vehicle-impact threat has been identified.

  • Groundworks and transitions designed around the specified products and site conditions.

I always advise treating these elements as one perimeter line. Ask how a proposed solution handles gate openings, corners, changes in level, foundations and connections between different products, not just how an individual panel performs.

Illustrative view of a data centre gate and perimeter, showing fencing, controlled access and bollards as distinct security measures

A practical decision checklist for your 2026 specification

Before approving a crash-rated system or perimeter tender, work through these steps:

  1. Define the threat. Record whether the concern is vehicle impact, forced entry, or both.

  2. Commission a VDA if a vehicle threat is credible. Use its findings to establish the vehicle, speed, angle and relevant approach.

  3. Specify the right evidence for each threat. Request vehicle-impact test evidence for VSBs and appropriate forced-entry certification, such as LPS 1175, for fencing or gates where required.

  4. Check the tested configuration. Confirm that the proposed product, layout, fixings and installation conditions are consistent with the evidence being relied on.

  5. Review the complete perimeter. Include gates, corners, transitions and access points in the design discussion.

  6. Request a detailed written scope. It should identify the products, installation responsibilities, groundworks and any assumptions or exclusions.

A low quote that does not explain its materials, installation scope or evidence can leave you with gaps that are difficult to identify until the project is underway. Compare the specification and written details, not only the headline price. I always recommend consulting security and engineering specialists on the site-specific assessment and performance requirements.

Making a proportionate perimeter decision

The best answer to “Do we need crash-rated fencing?” is: only if your risk assessment supports vehicle-impact protection, and even then, check whether a barrier, bollard, gate or combination of systems is the appropriate response.

At Fenceways Group Ltd, we provide high-security perimeter fencing, industrial and automated gates, rising bollards and associated installation and groundworks for commercial and industrial clients, including data centres. We do not manufacture crash-rated barriers. Our role is to help clients coordinate the perimeter line and integrate suitable specified products into a practical installation, with groundworks managed as part of the project scope.

If you are reviewing a data centre boundary, explore our commercial fencing services or contact Fenceways to discuss the perimeter elements and installation scope. We provide nationwide UK coverage from our Manchester and London offices.

 
 
 